What is API 622?
The API 622 standard is applicable to comparative testing of valve packings for process applications considering fugitive emissions, with a testing temperature range of -29°C to 538°C (-20°F to 1000°F). Key factors covered by the standard that affect fugitive emission performance include temperature, pressure, thermal cycling, mechanical cycling, and corrosion.
The standard is applicable to packing testing for the following types of valves:
Rising stem valves - the stem moves only axially
Rotating stem valves - the stem rotates 90°
Rising-and-rotating stem valves - the stem moves both axially and rotationally
| Test Item | Test Conditions | Acceptance Criteria | Test Duration |
|---|---|---|---|
| Fugitive Emission Test | 4137 kPag, 260°C, 1510 mechanical cycles | Static leakage ≤ 100 ppmv | 6 days |
| Ambient Corrosion Test | 30 MPa compressive stress, demineralized water | Surface corrosion assessment | 28 days |
| High-Temperature Corrosion Test | 149°C, 45 bar, demineralized water | Surface corrosion assessment | 35 days |
| Packing Material Test | Weight loss, density, lubricant content, etc. | Material properties meet requirements | According to specific tests |
Technical Requirements for Fugitive Emission Testing
Fugitive emission testing is the core content of the API 622 standard, evaluating the sealing performance of the packing system by simulating actual operating conditions. The test apparatus uses a horizontally mounted test stem to simulate the working environment of a typical valve stuffing box.
Test Apparatus Specification Requirements
The standard specifies two sizes of test apparatuses: the 1/8-inch packing test apparatus and the 1/4-inch packing test apparatus. Key dimensional requirements are as follows:
| Parameter | 1/8-inch Packing Apparatus | 1/4-inch Packing Apparatus |
|---|---|---|
| Stem Diameter | 11.05-11.1 mm | 25.2-25.4 mm |
| Stuffing Box Diameter | 17.46-17.52 mm | 38.1-38.35 mm |
| Stem Surface Roughness | 0.40-0.80 μm Ra | 0.40-0.80 μm Ra |
| Stuffing Box Depth | 19.05 mm ± 1.57 mm | 34.9 mm ± 1.57 mm |
Test Procedure and Cycling Requirements
The test procedure includes 1510 mechanical cycles and 5 thermal cycles, using dry methane gas with a purity of not less than 97% as the test medium. The test pressure ranges from 0 to 4137 kPag (0-600 psig), and the temperature ranges from ambient temperature to 260°C (500°F).
Mechanical cycling requirements vary according to the type of stem movement:
Rising stem: rate of 3-5 mm/s, stroke determined according to packing specifications
Rotating stem: rate of 10-15°/s, rotation angle of 90°±5°
Rising-and-rotating stem: combination of both movements
Technical Requirements for Corrosion Testing
Corrosion testing evaluates the corrosion effect of the packing on stem materials, including two parts: ambient temperature corrosion testing and high-temperature corrosion testing.
Ambient Temperature Corrosion Testing
The test is conducted at 22°C ± 11°C for 28 days. The test apparatus uses a compression fixture to apply a compressive stress of 30 MPa ± 0.69 MPa between the packing and metal specimens. Packing samples need to be soaked in demineralized water for 24 hours before testing.
High-Temperature Corrosion Testing
The high-temperature test is conducted at 149°C ± 17°C and 45 bar ± 2.25 bar for 35 days. The test apparatus is made of carbon steel and equipped with electric heating elements or heating blankets.
Corrosion Test Report Requirements
The corrosion test report must include the following:
Micrographs of each sample at 100x and 200x magnifications
A descriptive report on the degree of stem pitting, assessed in 10% surface area increments
A descriptive report on the degree of adhesion, assessed in 10% surface area increments
Technical Requirements for Packing Material Testing
Packing material testing evaluates the basic physicochemical properties of the packing, including indicators such as weight loss, density, lubricant content, and leachables.
Graphite Packing Ring Weight Loss Test
The test uses a stepwise heating method, starting from 150°C, increasing in 56°C (100°F) increments up to 538°C (1000°F), and finally holding at 593°C (1100°F) for 24 hours. Weight changes are measured after each temperature stage is held for 1 hour.
Density Determination
Braided packings and molded packing rings use different volume calculation methods:
Braided packing: volume = median length × width × thickness
Molded packing ring: volume = π × (outer diameter² - inner diameter²) × ring thickness / 4
Lubricant Content Determination
The Soxhlet extraction method is used to determine the wet lubricant content, using dichloromethane as the solvent, with an extraction time of approximately 16 hours. The PTFE content is calculated by determining the total fluorine content and dividing by a reference coefficient of 0.76.
Test Equipment and Calibration Requirements
API 622 imposes strict requirements on the performance and calibration of test equipment to ensure the accuracy and comparability of test results.
Leak Detection Equipment Requirements
An organic vapor analyzer with flame ionization function must be used. Performance requirements include:
Maximum repeatability: ±2.0 ppmv within the 0-100 ppmv range
Minimum detection level: ≤1.0 ppmv
Maximum response time: 15 seconds (from 0 ppmv to 100 ppmv)
Maximum recovery time: 10 seconds (returning to 10% of the initial value)
Sampling flow rate: 0.25-1.5 l/min
Calibration Requirements
Leak detection equipment must be calibrated daily using porous or sintered metal/ceramic leak standards. The calibration standards should be within a methane flow rate range of 0.050 ml/min to 0.100 ml/min, and calibration verification must be performed at least once a year.
Packing Qualification and Recertification Requirements
According to Chapter 7 of the standard, any change in the design of the packing system requires recertification, including but not limited to:
Changes in packing/seal materials
Changes in packing/seal manufacturers
Changes in packing/seal models
Changes in packing manufacturing locations
This requirement ensures the consistency and reliability of packing performance, preventing unverified changes from affecting sealing performance in practical applications.
Report Requirements and Document Management
An acceptable API 622 packing report must include the forms specified in Annex B:
Fugitive emission test report (Table B.1) - static leakage not exceeding 100 ppmv and no stem seal adjustment
Complete ambient and high-temperature corrosion test data sheets (Tables B.2 and B.3)
Complete material test data sheet (Table B.4)
All test records must be complete, accurate, and traceable. Testing facilities must maintain current records of test equipment calibration.
Standard Implementation Recommendations and Best Practices
Based on the technical requirements of the API 622 standard, the following implementation recommendations are proposed:
Packing Selection Recommendations
When selecting valve packings, priority should be given to products that have passed API 622 certification. A tested packing with a cross-section of 3.2 mm (1/8 inch) can certify all cross-sections from 3.2 mm to 6.3 mm, while a tested packing with a cross-section of 6.3 mm (1/4 inch) can certify all cross-sections of 6.3 mm and above.
Test Plan Development
It is recommended to develop a detailed test plan, including:
Clear test objectives and acceptance criteria
Selection of a suitable test laboratory
Ensuring the representativeness and traceability of test samples
Establishing a complete document management system
Practical Application Considerations
Although API 622 provides standardized testing methods, the following still need to be considered in practical applications:
Actual operating conditions may differ from test conditions
Packing installation quality has a significant impact on performance
The necessity of regular maintenance and inspection
Operator training and qualification requirements