What is the API 607 fire safe test procedure?

 

API 607, short for "Fire Resistance Testing of Rotary and Actuated Valves," is a crucial technical specification developed and published by the American Petroleum Institute (API). Its core value lies in simulating real-world fire scenarios to put valves to extreme tests of their sealing performance, structural integrity, and operational capability. This verifies whether valves can continue to perform their essential function-isolating fluids and preventing catastrophic leaks-during and after a fire. This not only imposes stringent quality requirements on valve products but also significantly strengthens the safety defenses of entire industrial facilities.

This standard primarily applies to specific types of valves, namely "rotary valves." These valves are characterized by their opening and closing elements (such as valve discs, balls, and butterfly plates) rotating around a valve shaft to achieve opening or closing. Specifically, the scope of API 607 ​​includes, but is not limited to:

Ball valves: Whether floating or fixed ball structures, these are among the most common valves in industrial applications requiring compliance with API 607.

Butterfly valves: Especially centerline, double-eccentric, and triple-eccentric butterfly valves used for critical media isolation.

Plug valves: Including lift-type and conventional plug valves.

 

Key Process of Fire Resistance Test (API 607 Standard)‌

The fire resistance test specified by API 607 is a highly procedural and standardized process designed to ensure the fairness, repeatability, and comparability of test results. The entire test procedure can be broken down into the following key stages:

 

‌1. Pre-Test Preparation & Initial Performance Verification‌

The valve under test must be installed in the test piping system as required by the standard, with the valve body filled with water and subjected to the rated pressure.

Before igniting the flame, perform seat sealing performance and operational tests at room temperature, recording initial leakage data and operating torque to ensure the valve is in good condition before the test.

 

‌2. High-Temperature Burning Phase‌

This is the core phase of the test. The valve is completely surrounded by flames from two or more gas burners, exposing critical components such as the valve body, bonnet, and stem to temperatures ranging from ‌750°C to 1000°C‌.

The burning process typically lasts ‌30 minutes‌. During this time, the valve must continuously withstand internal water pressure while closely monitoring two key indicators:

‌High-temperature leakage rate through the seat‌ (internal leakage when the valve is closed).

‌External leakage rate‌ (leakage from the valve body, bonnet, stem, etc.).

‌

3. Forced Cooling & Post-Operational Testing‌

Immediately after the 30-minute burning phase, the valve undergoes ‌forced water cooling‌ to simulate the effect of fire sprinklers.

Once the valve temperature drops below ‌100°C‌, a ‌post-operation performance test‌ is conducted.

The operator must attempt to open the valve from the closed position to fully open and then close it back to fully closed under pressure.

This test verifies whether the valve's driving and transmission mechanisms can still perform basic opening and closing actions after exposure to fire and cooling.

 

‌4. Final Hydrostatic Strength Test‌

After the post-operation test, the valve is closed again and subjected to a ‌higher-pressure hydrostatic test‌.

The test pressure is increased to ‌1.5× or 2×‌ the valve's rated pressure at room temperature (depending on the standard version and valve class) and held for a specified duration.

This step thoroughly examines whether the valve's structural integrity-including the valve body, bonnet, and connections-remains reliable after extreme thermal cycling.

‌

Core Acceptance Criteria & Performance Judgment‌

A valve passes the API 607 fire resistance test only if it meets the strict acceptance criteria specified in the standard. The key indicators are summarized in the table below:

‌Test Item‌ ‌Acceptance Criteria‌ ‌Explanation‌
‌High-Temperature Leakage Rate (Internal Leakage)‌ Leakage through the seat ≤ ‌100 mL/min‌ during the 30-minute burning phase. Ensures the valve maintains basic sealing capability to prevent significant media leakage.
‌External Leakage Rate‌ Total leakage from the valve body, bonnet, stem, etc. ≤ ‌100 mL/min‌. Limits external leakage to prevent flame spread and protect surrounding equipment and personnel.
‌Post-Operation Performance‌ The valve must successfully open from closed to fully open and then close back under pressure. Ensures the valve retains its isolation function after a fire incident.
‌Final Hydrostatic Strength‌ No visible leakage or structural failure at ‌1.5× or higher‌ rated pressure. Confirms the valve's structural strength still meets safety margin requirements after extreme testing.

Only when all the above indicators meet the requirements can the valve be considered compliant with the API 607 standard and be appropriately marked on the product nameplate or related documents.

 